Power Factor Improvement by Capacitive VAR Compensation - Power System Analysis Lab
Laboratory Title
Power Factor Improvement
by Capacitive VAR Compensation
Objective
The purpose of this
experiment is to demonstrate the power factor correction procedure at a
customer bus bar for three-phase loads.
Apparatus
1.
Lab volt Setup
2.
3 Phase Resistive Load
3.
3 Phase Inductive Load
4.
Power Supply Unit
5.
Connection Wires
6.
Data Acquisition and Control Interface
7.
Host Computer
Procedure
1.
At the beginning, all the equipment were
connected according to the figure. The power supply was used to implement the
AC power source. And, the resistive and inductive load were used to implement
the 3 phase load. The capacitive load was used to implement the 3 phase
capacitor.
2.
Then, the Y- connected 3 phase load was
set as 960Ω and, the reactance of the each inductor was set to 686Ω using
switches.
3.
The reactance of the 3 phase capacitor was
kept equal to infinite.
4.
The 240V (Line-to-Line) 50 Hz power supply
was connected to the 3 phase load.
5.
Then, the system was powered up and follow
measurements were taken using the host computer.
l Line-to-line
voltage (E1, E2)
l Line
Current (l1, l2)
l Total
Active Power
l Total
Reactive Power
l Total
Apparent Power
l Power
Factor (El1, El2)
6.
Then, the capacitive load was set as Power
Factor is as close as possible to unity using the switches.
7.
Again, all the measurements were taken for
this case and the reactance of the each capacitor also.
8.
Then, the measurements of with capacitors
and without capacitors were compared.
Observations
Discussion
3.
Power factor correction (PFC) aims to improve power
factor, and therefore power quality. It reduces the load on the electrical
distribution system, increases energy efficiency and reduces electricity costs.
It also decreases the likelihood of instability and failure of equipment.
In power factor correction the
procedure is to reduce the lagging power factor in inductive loads by fixing a
high value capacitor across the phase and neutral close to the load. Power
factor correction is obtained via the connection of capacitors which produce
reactive energy in opposition to the energy absorbed by loads such as motors,
locally close to the load. When the Voltage and Current are in phase with each
other in an AC circuit, the energy from the source is fully converted into
another form to drive the load and in this case power factor is in unity. This
improves the power factor from the point where the reactive power source is
connected, preventing the unnecessary circulation of current in the network. When
the power factor drops, the system becomes less efficient.
4.
The major effect of poor power factor is higher value
of line current. We know that power factor (pf) is an important parameter for
calculation of power in an AC circuit. For a given power and voltage, the
current flowing through the line is inversely proportional to the power factor.
This means that a poor power factor i.e. low power factor will result in higher
load current and hence higher losses.
The four detrimental effects of
low power factor on the distribution system of the are the following.
·
Large Copper Losses
·
Requirement of large kVA Rating of Equipment
·
Greater Conductor Size
·
Poor Voltage Regulation
·
Requirement of large kVA Rating of Equipment
Electrical equipment / machines are generally
rated in kVA. But as per the power triangle
∴ CosØ = P / S = kW / kVA
⇒ kVA = kW / CosØ
Thus, lower value of CosØ will lead to higher
value of kVA rating. This in turn will result in higher machine losses.
Therefore the size of machine will increase and hence its cost will also
increase.
- Greater
Conductor Size:
Poor power factor is not only important for loads
but it also plays an important role is power transmission. As discussed, low
power factor causes higher line current. As the current carrying capacity of a
conductor is directly proportional to its cross-sectional area, higher current
will require greater conductor size. Thus the size of transmission conductor
increase.
- Large Copper
Losses:
Ohmic loss (I2r loss) is also known as
copper loss. Larger current due at low power factor causes more ohmic loss and
hence reduced efficiency.
- Poor Voltage
Regulation:
Percentage Voltage Regulation of Transmission
Line is given as
% Voltage Regulation = [(VS – VR)
x100/ VR ] %
Since large line current causes larger voltage
drop in the line impedance. Therefore the receiving end voltage (VR)
will be much lower than the sending end voltage (VS). Hence voltage
regulation will be poor.
3.
Because the Energy stored depends on
the square of the voltage. So using DELTA ensures line-line voltage and more
reactive energy stored than in STAR using phase voltages.
Typically line to phase voltage is √3 larger and since E=0.5CV2 it ensures 3 times the energy
connected in DELTA than STAR for the same value of capacitance.
Comments
Post a Comment